Thermocouple Selection
1. Depress and hold button down and then apply
power to the unit.
2. Release button.
3. Depress button one, two or three times to select specific
thermocouple type. (Model dependant. For Model SEM203TC-1: once
for "K", twice for "J", three times for
"T"). The LED will blink with each depression.
After several seconds the LED will flash the number times corresponding
to the TC selected.
|
Ranging
1. Connect a thermocouple simulator to input
and a 24 VDC power supply to output.
2. Set the simulator to the temperature desired at 4ma. Press and
HOLD the button down until the LED starts to blink and then release.
3. Set the simulator to the temperature desired at 20ma. Press
and release the calibration button. The LED blinks and then stops,
confirming the unit is calibrated.
|
ORDER CODE
.SEM203TC/1
Thermocouples K, J, & T
.SEM203TC/2
Thermocouples R, S, & B
.SEM203TC/3
Thermocouples J, F, & E
.SEM203TC/4
Thermocouples K, N, & R
.For
SEM203TC Special Configuration Ranges and Downscale Burnout
.please
contact sales office. |
SPECIFICATION @ 68 °F
INPUT / OUTPUT SENSORS AND RANGES
| .INPUT |
.SEM203TC |
| .Sensor
& Range |
.SEM203TC/1
.K (-328 to 2498°F)
.J (-328 to 2192°F)
.T (-328 to 752°F)
.SEM203TC/2
.R (0 to 3200°F)
.S (0 to 3200°F)
.B (0 to 3308°F)
.SEM203TC/3
.J (-328 to 2192°F)
.F (-328 to 2192°F)
.E (-328 to 1832°F)
.SEM203TC/4
.K (-328 to 2498°F)
.N (32 to 2372°F)
.R (32 to 3200°F)
.Other combinations available
.to special order |
| .Default
Range |
.203TC/1 = K (0 to
1832°F)
.203TC/2 = R (0 to 2912°F)
.203TC/3 = J (0 to 1832°F)
.203TC/4 = K (0 to 1832°F) |
| .Accuracy |
.±0.04% FS, ±0.04% Rdg
or 0.9°F
.(which ever is greater) |
| .Linearization
Standard |
.BS4937 / IEC 584-1 |
| .Input
/ Output Isolation |
.50VDC
(tested to 200V) |
| .Cold
Junction Error |
.±0.3°F |
| .Cold
Junction Tracking |
.0.03°F/°F |
| .Cold
Junction Range |
.-4 to 158°F |
| .Thermal
Drift |
.Zero = ±2.3µV/°F
Typical |
| .Span = 100 ppm |
| .Sample Rate |
.500ms
per sample |
| .Minimum
Span |
.20°F |
| .Sensor
Lead Length |
.Max
length 10 feet to Maintain CE Compliance |
| .Terminals |
.Screw Terminals |
OUTPUT
| .Output
Range |
.4 to 20
ma - 2 Wire Loop Powered
.(Can be ranged
20 to 4 ma) |
| .Max. Output
Range |
.3.8 to 22 ma |
| .Operating
Voltage |
.8 to 30 V |
| .Accuracy |
.±5 µA |
| .Burnout |
.Up-Scale 22ma
(Down-Scale to order)
.Red programming LED comes on when
.temperature is outside operating range |
| .Thermal drift |
.0.17 µA/°F |
| .Response
Time |
.500 ms to Reach 70% of
Final Value |
| .Loop
Resistance |
.Max. 800 ohms @ 24 VDC |
| .Loop Sensitivity |
.0.4 µA/V |
| .Protection |
.Reverse connection
protected |
| .Terminals |
.Screw Terminals |
| .Warm-up
Time |
.2 minutes to full
accuracy |
| .Display |
.Slow flash
indicates programming mode
.Full on indicates out of range
sensor |
| .Switch |
.Momentary Push
Button |
APPROVALS
| .EMC |
.Emissions |
.BS EN 50081-1 |
| .Susceptibility |
.BS EN 50082-2 |
ENVIRONMENTAL
| .Ambient
operating range |
.-4 to 158 °F |
| .Ambient storage
temperature |
.-40 to 194 °F |
| .Ambient
humidity range |
.0 to 95% RH
(non-condensing) |
ENCLOSURE
| .Material |
.ABS |
| .Flammability |
.UL 94 HB |
| Calibration Period |
.12 months to maintain
published specifications.
.5 years to twice specifications. |
| Warranty |
.5 years |
DOWNLOADS
SEM203TC Instruction Manual
SEM203TC
Literature
|