INPUT SPECIFICATION @ 68 °F
| .Thermocouple Types |
.J, K, N, R, S, T |
| .Millivolt |
.-5 to 50 mv signals |
| .Isolation |
.INPUT to OUTPUT
.500 VDC (Flash tested to 1 kV) |
| .Burn
Out |
.UP scale standard (DOWN
scale to order) |
| .Impedance |
.> 1M ohm |
| .Cold
Junction |
.Automatic compensation may
be selected for use with T/C types indicated or fixed zero
compensation may be selected for mv or differential T/C measurement. |
| .CJ
Accuracy |
.±0.4 ºF @ 68 ºF ±0.02
ºF/ºF Typical |
OUTPUT
| .Type |
.Passive 2
wire current output |
| .Range |
.4 to 20 ma (30 ma max.) |
| .Linearity |
.mv input linearity ±0.005%
.T/C ranges are cold junction compensated
and directly referenced to T/C mv values. |
| .Protection |
.Reverse connection plus
over voltage |
GENERAL SPECIFICATIONS
| .Supply |
.10 to 30 VDC |
| .Load |
.700 ohms @ 24 V |
| .Thermal
Stability |
.1 µV/ºF
.plus cold junction errors |
| .Ripple Refection |
.<40 µA/V (measured at
1 V ripple 60 Hz) |
| .Response time |
.200 ms to reach 70% of
final value |
| .Operating
Temperature |
.Ambient 32 to 158 ºF |
| .Relative Humidity |
.Ambient 10-95%
non-condensing |
APPROVALS
| .Tested to: |
|
| .IEC 801-2 |
.Susceptibility to
electrostatic discharge |
| .IEC 801-3 |
.Radiated Susceptibility |
| .IEC 801-4 |
.Susceptibility to
conducted interference |
| .EN 55022 |
.Radiated emissions |
ENCLOSURE
| .Case
Material |
.Polyamide (Grey) |
| .Case
Flammability |
.To UL94-VO VDE 0304 Part 3
Level IIIA |
| .Mounting |
.Top Hat rail to DIN EN
50022-35 |
| .Protection |
.IP20 |
| .Connections |
.Captive screw connections |
| .Cable
Size |
.12 AWG solid / 14 AWG
stranded |
STANDARD RANGES
The SEM1500TC may be
purchased pre-ranged to any of the following standard ranges:
Range ºF
from to |
Range ºC
from to |
THERMOCOUPLE TYPE |
millivolt
V |
| N |
K |
T |
J |
R |
S |
| 32 212 |
0 100 |
* |
* |
* |
* |
|
|
|
| 32 392 |
0 200 |
* |
* |
* |
* |
|
|
|
| 32 752 |
0 400 |
* |
* |
* |
* |
|
|
|
| 32 1112 |
0 600 |
* |
* |
|
* |
|
|
|
| 32 1472 |
0 800 |
* |
* |
|
* |
|
|
|
| 32 1832 |
0 1000 |
* |
* |
|
|
* |
* |
|
| 32 2192 |
0 1200 |
* |
* |
|
|
* |
* |
|
| 32 2912 |
0 1600 |
|
|
|
|
* |
* |
|
Range mv
0 50 mv |
Range mv
0 50 mv |
|
* |
NON STANDARD RANGES
Units can be supplied set up to other non-standard ranges for a
small extra charge or alternatively the unit can easily be re-ranges as follows:
ADJUSTMENTS (Range selection)
Range selection GAIN and OFFSET Coarse settings are made by two 16 position
rotary screw adjustment switches on the side of the unit. Fine adjustment
is by front access potentiometers. Full re-calibration details are
supplied with each transmitter.
| INPUT type |
OFFSET
RANGE ºF |
GAIN
RANGE ºF |
OFFSET
RANGE ºC |
GAIN
RANGE ºC |
| |
at 4 ma |
4 to 20 ma |
at 4 ma |
4 to 20 ma |
| K T/C |
-328 to 752 |
212 to 2192 |
-200 to 400 |
100 to 1200 |
| T T/C |
-328 to 752 |
212 to 2192 |
-200 to 300 |
100 to 400 |
| J T/C |
-328 to 752 |
158 to 1382 |
-200 to 400 |
70 to 750 |
| N T/C |
392 to 752 |
302 to 2192 |
200 to 400 |
150 to 1200 |
| R T/C |
32 to 1832 |
932 to 3092 |
0 to 1000 |
500 to 1700 |
| S T/C |
32 to 1832 |
932 to 3200 |
0 to 1000 |
500 to 1760 |
| V mv |
-5 to +15 mv |
3 to 50 mv |
-5 to +15 mv |
3 to 50 mv |
DOWNLOADS
SEM1500TC Instruction Manual
SEM1500TC Literature
ORDER CODE
| SEM1500 /
Input Type / |
value @ 4 ma
/ |
value @ 20 ma
/ |
ºF or ºC |