High Accuracy / 0.05%
Small Size / High Packing Density
DIN Rail Mount
Loop Splitter

ONE 4 to 20 ma INPUT SPLIT INTO
TWO FULLY ISOLATED 4 to 20 ma OUTPUTS
SEM1200

INTRODUCTION
The SEM1200 is an isolator that provides TWO isolated 4 to 20 ma outputs from a single 4 to 20 ma input.  The input and the output loops must each have power supplies.  The three power supplies (V1, V2 & V3) must of course be isolated from each other to maintain isolation.  The isolator is housed inside a plastic enclosure, suitable for DIN Rail mounting.  Screw terminals are provided for wire connections.

 

V1 and V2 and V3 = Can all be up to 30 VDC each

Input Loop Voltage Drop = 5 Volts Typical

Each Output Voltage Drop = 6 Volts Typical

Note: Load must be >250 ohms for ambient > 122ºF.  This will dissipate power in the loop and minimize isolator self heating.

GENERAL SPECIFICATIONS @ 68ºF

.Input Range .4 to 20ma
.Isolation .1000 VAC RMS (Flash tested to 3 KV)
.Accuracy .0.05% (including Hysteresis and Linearity)
.Stability .P60 ppm/ºF
.Ambient .32-158 ºF, 10-95% RH non-condensing
.Time Constant .0.1 sec (to 63% of final value)
.Adjustments .Front entry Zero & Span Potentiometers

APPROVALS

.EMC .TESTED TO:
.IEC 801-2 .Susceptibility to electrostatic discharge
.IEC 801-3 .Radiated Susceptibility
.IEC 801-4 .Susceptibility to conducted interference
.EN 55022 .Radiation emissions

MECHANICAL

.Mounting .DIN Rail
.Connections .Captive terminal screws
.Cable size .12 AWG solid / 14 AWG Stranded
.Flammability .UL94-V0, VDE 0304 Part 3 Level IIIA