 | High Accuracy 0.05%
 | 3 Port Galvanic Isolation
 | DIN Rail or Surface Mount
 | User Selectable Input and Output
 | AC or DC Powered |
| | | |
|
DC - DC ISOLATOR / CONVERTER
SEM1100
|
INTRODUCTION
The SEM1100
is an isolating converter that accepts most
common high level process signals (current and voltage), isolates them
electrically and physically, and converts them to another process
signal. It is also possible to have voltage and current outputs
simultaneously from a single input.
The isolator is available in AC and DC powered
versions, both generating loop excitation for input and output loops
at the same time.
Zero and span adjustment potentiometers are
conveniently situated on the front panel together with a power ON LED.
Configuration (factory set if specified) can easily be changed by
means of internal switches and the use of suitable equipment.
|
INPUT SPECIFICATION @ 68 °F
| .Current |
.4-20, 0-20 ma Active or
Passive (40 ma max.) |
| .Voltage |
.0-100 mv, 0-1, 0-5, 0-10V
(20 V max.) |
| |
.or 20-100 mv, 0.2-1, 1-5,
2-10 V (20 V max.) |
| .Selection |
.Internal Switches |
| .Impedance |
.Voltage = >1M ohm |
| |
.Current = <50 ohms |
| .Protection |
.Reverse connection / over
voltage |
| .Loop
Supply |
.25V @ 25ma
Nominal (available for input transmitter 27 V max.) |
OUTPUT
| .Current
* |
.4-20, 0-20 ma Active or
Passive |
| .Voltage
* |
.0-1, 0-5, 0-10 Volts** |
| .0.2-1, 1-5, 2-10 Volts*** |
| .Selection |
.Internal Switches |
| .Load |
.Current 0 to 1K ohm |
| .Voltage Max. current 5 ma |
| .Linearity |
.0.05% Full Range Output |
| .Stability |
.100 ppm/°F |
.Notes:
.*
Current and voltage outputs are not isolated from each other.
.**
Available simultaneously with 0-20 ma output
.*** Available
simultaneously with 4-20 ma output |
GENERAL SPECIFICATIONS
| .Supply |
.90-253 VAC 50/60 Hz or
20-35 VDC |
| .Power Consumption |
.4 Watts Max. |
| .Indication |
.Power on LED |
| .Response time |
.<100 ms for 70% of
final reading |
| .Protection |
.Internal Fuse 500 ma (T) |
| .Isolation
Input/Output |
.500 VDC (flash tested @ 1
kV) |
| .Supply |
.Flash tested @ 3 kV |
APPROVALS
| .EMC |
.Emissions |
.BS EN 50081 |
| .Susceptibility |
.BS EN 50082 |
| .Electrical Safety |
.UL 508 / BS EN 61010-1 |
MECHANICAL
| .Mounting |
.DIN rail or Surface Mount |
| .Ambient |
.32-122 ºF, 10-95% RH
non-condensing |
| .Connections |
.Captive terminal screws |
| .Cable size |
.12 AWG solid / 14 AWG
Stranded |
| .Flammability |
.UL94, V-0, VDE 0304 STEP
11b |
CONFIGURED RANGES AVAILABLE
| INPUT |
|
OUTPUT |
| 4-20
ma Passive |
|
VOLTAGE |
CURRENT |
| 4-20
ma Active |
|
0.0-1
VDC |
0-20
ma |
| 0-20
ma Passive |
|
0.2-1
VDC |
4-20
ma |
| 0-20
ma Active |
|
0.0-5
VDC |
0-20
ma |
| 0-100
mv |
|
1-5
VDC |
4-20
ma |
| 20-100
mv |
|
0-10
VDC |
0-20
ma |
| 0.0-1
VDC |
|
2-10
VDC |
4-20
ma |
| 0.2-1
VDC |
|
|
|
| 0.0-5
VDC |
|
|
|
| 1-5
VDC |
|
.Default
range:
.Input = 4-20 ma
.Output = 4-20 ma or 1-5 VDC |
| 0-10
VDC |
|
| 2-10
VDC |
|
DOWNLOADS
SEM1100 Instruction Manual
SEM1100 Literature
ORDER CODE
SEM1100 / S1 or S2 / ENC1
| .SEM1100
Basic Model Number |
| .Power
Options |
.S1 = 90-253 VAC or
.S2 = 20-35 VDC |
| .Optional
Enclosure |
.ENCL = NEMA 4
Enclosure holds four SEM1100 units. Size = 5" x 5" x 5" |
|