V1 = Up to 30 VDC
Isolator Output Circuitry Voltage Drop = 5 Volts Typical
| Maximum Load =... |
V1 - 5 V
- Tx Voltage Drop |
....K
ohms |
| 20 ma |
GENERAL SPECIFICATIONS @ 68ºF
| .Input Range |
.4 to 20ma |
| .Isolation |
.1000 VAC RMS (Flash tested
to 3 KV) |
| .Accuracy |
.0.05% (including
Hysteresis and Linearity) |
| .Stability |
.P60 ppm/ºF |
| .Ambient |
.32-158 ºF, 10-95% RH
non-condensing |
| .Time Constant |
.0.1 sec (to 63% of final
value) |
| .Adjustments |
.Front entry Zero &
Span Potentiometers |
APPROVALS
| .EMC |
.TESTED TO: |
| .IEC 801-2 |
.Susceptibility to
electrostatic discharge |
| .IEC 801-3 |
.Radiated Susceptibility |
| .IEC 801-4 |
.Susceptibility to
conducted interference |
| .EN 55022 |
.Radiation emissions |
MECHANICAL
| .Mounting |
.DIN Rail |
| .Connections |
.Captive terminal screws |
| .Cable size |
.12 AWG solid / 14 AWG
Stranded |
| .Flammability |
.UL94-V0, VDE 0304 Part 3
Level IIIA |
DOWNLOADS
SEM1010 Instruction Manual
SEM1010 Literature
ORDER CODE
SEM1010 Isolator
with Build-in Power Supply
|