  Model SEM164
±2% RH
Model SEM164
±3% RH
Model SEM165T/H
 
Model SEM165T/P
...RELATIVE HUMIDITY
.RH Range: 0 to 100% RH
Wettable
10 to 95% RH 0 to 100% RH
Wettable
0 to 100% RH
Wettable
.Temperature Range: -40ºF to +140ºF
(-40ºC to 60ºC)
-40ºF to +140ºF
(-40ºC to 60ºC)
-40ºF to +248ºF
(-40ºC to 120ºC)
-22ºF to +284ºF
(-30ºC to 140ºC)
.Accuracy: ± 2% RH ± 3% RH ± 2% RH ± 2% RH
.Hysteresis: <1.7% <2% <1.7% <1%
.Response Time:
.(Step Change T90)
<6 seconds <15 seconds <6 seconds <10 seconds
.Linearity: ± 1.5%
(0 to 98% RH)
± 2%
(20 to 95% RH)
± 1.5%
(0 to 98% RH)
± 2.5%
(11 to 90% RH)
.Pressure: N/A N/A 400 psi Max. 400 psi Max.
.Output: 4 to 20 mA
0 to 100% RH
4 to 20 mA
0 to 100% RH
4 to 20 mA
0 to 100% RH
4 to 20 mA
0 to 100% RH
...TEMPERATURE
.Sensor: Pt100 Pt100 Pt100 Pt100
.Accuracy: 0.5ºF ± 0.1% reading 0.5ºF ± 0.1% reading 0.5ºF ± 0.1% reading 0.5ºF ± 0.1% reading
.Output: 4 to 20mA (32/212ºF) 4 to 20mA (32/212ºF) 4 to 20mA (32/212ºF) 4 to 20mA (32/212ºF)
...GENERAL - HEAD ELECTRONICS
.Ambient Operating Range: -4ºF to 131ºF
5 to 95% RH
(non-condensing)
-4ºF to 131ºF
5 to 95% RH
(non-condensing)
-4ºF to 131ºF
5 to 95% RH
(non-condensing)
-4ºF to 131ºF
5 to 95% RH
(non-condensing)
.Supply Voltage 10 to 32 VDC 10 to 32 VDC 10 to 32 VDC 10 to 32 VDC
.Load (Vs-10) 22 = K ohms (Vs-10) 22 = K ohms (Vs-10) 22 = K ohms (Vs-10) 22 = K ohms
...APPROVALS
.Emmissions BS EN 61326 BS EN 61326 BS EN 61326 BS EN 61326
...DOWNLOADS:
.Literature LIT LIT LIT LIT
.Instruction Manual soon soon soon soon
 

 