Lowest cost
process meter
 |
Broad scaling
capability
 |
4-20mA,
10-50mA, or 1-5mA I/P
 |
Very
competitive pricing
 |
Fast
deliveries, normally in stock
 |
Normal or
inverted scaling
 |
Simple and
attractive facial design
 |
Extra x10 and
x100 digits
 |
High quality
plug-in terminals
 |
Units-of-measure
label fitted
 |
Low loop drop
2.5V max
|
| | | | | | | | | |
|
| Connection
Example |
| The 88-Pro may be
connected to a wide range of signal loops, without additional
auxiliary or loop excitation power supplies, because the meter
is self powered and drops only 2.5V in the loop.

The simple example
shown could be used for measuring the contents of a straight
sided liquid storage tank. The transmitter would be sited near
the bottom of the tank, and as liquid level rises, so the
pressure at the base would rise. The meter's broad scaling
capabilities allow it to be adjusted to read in true volume.
|
|
 |
| · |
The
88-Pro displays a wide range of process variables such as
temperature, pressure, flow, weight, pH, humidity, etc. It
accepts most process signals, such as 4-20mA and 1-5mA, and
gives superb value for money. |
| · |
The loop
voltage drop is only 2.5V |
| · |
The
simple bezel will compliment your panel design. The lens
protects all legends and markings, so repeated wipe-downs
won't damage the lettering or display clarity. High contrast
LCDs make these meters suitable for use in bright
environments. |
| · |
You can
extend the maximum reading up to 19990 or 199900 with fixed
zeros, selected by jumper switches. This is useful when the
cost of a 4 1/2 or 5 1/2 digit meter may be too high. |
| · |
There's
also an INVERT facility, so an increasing input signal gives a
reducing display, for example 4-20mA=100.0 to 0.0. |
| · |
The case
depth is less than that of our other process meters, saving
you valuable space in the panel.
<<
BACK TO ELECTRONICS
|
|

|
| The
design of the connectors means that no extra depth is required
for cable loops. The cable exits the bottom surface of the
connector, not the rear. |
Panel
Cutout
45mm high, 92mm wide
Tolerances +1mm, -0mm
Bezel Size=48x96mm
|
|
|
| Input
Ranges: |
| Range |
Effective
I/P Resistance |
| 4-20mA |
125 Ohms |
| 10-50mA |
50
Ohms |
| 1-5mA |
500 Ohms |
|
|
| All range
selection jumpers may be accessed from the rear of the meter without
needing to open the case. |
| Specifications: |
| Digital
Height |
12.7mm
standard |
| Display
Type |
High
contrast LCD |
| Accuracy |
+/-0.1% of
range |
| Calibration
Method |
Zero
+ Span pots |
| Decimal
Point Selection |
push-on
jumpers |
| CMRR |
65
dB DC-450Hz |
| Linear
Ranges |
3-21mA,
8-52mA, 0.8-6mA |
| Resolution |
1
part in 2000 max. |
| Display
Update Rate |
3
readings/second |
| Technique |
dual
slope integrator |
| Integration
Period |
100mS |
| Temperature
Range |
-10
to +50 degrees C |
| Sealing
Rating at Bezel |
IP54 |
|
|
| Ordering
Guide: |
| Simply state
model 88-Pro. |
| Specify input
signal range and desired display range. |
| Specify units of
measure (Kg, Bar, degrees C, etc). |
| (You may change
calibration yourself via the zero and span pots) |
| Optional IP67
cover available, specify model SPC4. |
|