All alarms can be: High, Low or Deviation and have
programmable hysterisis. They can be set to fail safe high or low and can
be latching or non-latching. The analog output can be any part of the
input range.
In the DM4000A and C versions the relay output can be
programmed to give a 100 ms output at decade intervals from the TOTAL display.
(e.g.. every 10 GAL or 100 GAL etc.)
OPTIONS SPECIFICATIONS @ 68 °F
| .OPTION
01 |
.Single
Relay Output Card |
| .Relay |
.Single
programmable alarm relay.
.Normally open and normally closed output
available. |
| .Rating |
.8 amps @ 240
V |
| .Isolation |
.500 V with
respect to inputs* |
| |
| .OPTION
02 |
.Dual
Relay Output Card |
| .Relay |
.Two
independently programmable alarms sharing the same common. |
| .Rating |
.8
amps @ 240 V |
| .Isolation |
.500
V with respect to inputs* |
| |
| .OPTION
03 |
.Current
Output |
| . |
.The
output can be driven by either an internal or external power source. |
| .Accuracy |
.<0.1%
of full scale |
| .Resolution |
.<0.1%
of full scale (>10% of the input range) |
| .Power |
.Internal
supply will drive into 700 ohms
.External loop voltage 10 to 30 VDC |
| .Isolation |
.500
V with respect to inputs* |
| .Response |
.<100
ms for 63% step change |
| .Output |
.Minimum
0 ma
.Maximum 22 ma |
| |
| .OPTION
04 |
.Bridge
Excitation (Strain Gage) |
| |
.This
provides either a programmable 2 to 20 VDC output
.or a fixed 24 VDC stable output |
| .Range |
.2
to 24 VDC |
| .Accuracy |
.<0.1%
of full scale |
| .Isolation |
.500
V with respect to inputs* |
| .Stability |
.<56
ppm/ºF |
| .Output |
.50
ma max. (less current consumed by other output slot) |
| .Ripple |
.<0.05%
full scale @ 50 ma |
| NOTES.... |
..*
Isolation is supplied between inputs, outputs and communication slots
but not between two analog output slots. |
ENVIRONMENTAL SPECIFICATION
| .Ambient
Temp. Range |
.32 to 122 ºF |
| .Relative
Humidity |
.5 to 95% RH non-condensing |
| .Isolation |
.Inputs fully isolated 500
V |
| .Power
Supply |
.120 VAC 50/60 Hz
.240 VAC 50/60 Hz
.24 VAC 50/60 Hz
.fully isolated to 1.5 KV |
DM4000U - UNIVERSAL
INPUT PROCESS INDICATOR
The DM4000U
is a universal digital indicator which can be configured
from the front panel to take all common industrial sensors without the need to
change option boards or move jumpers. There are two output slots which can
accept any of the optional output boards.
DM4000U SPECIFICATIONS @ 68 °F
| .THERMOCOUPLE |
± ACCURACY*
|
RESOLUTION** |
NOMINAL RANGE
|
| .TC Type K |
2 ºF |
0.1 ºF |
-454 to 2192 ºF |
| .TC Type J |
2 ºF |
0.1 ºF |
-346 to 1400 ºF |
| .TC Type T |
2 ºF |
0.1 ºF |
-454 to 752 ºF |
| .TC Type R |
4 ºF |
0.5 ºF |
+32 to 3182 ºF |
| .TC Type S |
4 ºF |
0.5 ºF |
+32 to 3182 ºF |
| .TC Type E |
2 ºF |
0.5 ºF |
+32 to 1202 ºF |
| .TC Type F |
2 ºF |
0.5 ºF |
+32 to 1112 ºF |
| .TC Type N |
2 ºF |
0.5 ºF |
+32 to 2372 ºF |
| .TC Type B |
4 ºF |
0.5 ºF |
+1832 to 3272 ºF |
| .Cold Junction |
1 ºF |
0.1 ºF |
+32 to 122 ºF |
|
.RTD
|
± ACCURACY
|
RESOLUTION |
NOMINAL RANGE
|
| .Pt100 |
0.2 ºF±0.1% of reading |
0.02 ºF |
-328 to 1472 ºF |
|
.VOLTAGE
|
± ACCURACY
|
RESOLUTION |
NOMINAL RANGE
|
| .10 Volts |
0.02% of full scale |
0.004% |
-10 to +10 V |
| .1 to 5 Volts |
0.04% of full scale |
0.008% |
1 to +5 V |
| .1 volt |
0.02% of full scale |
0.004% |
±1 V |
| .100 mV |
0.02% of full scale |
0.004% |
±0.1 V |
|
.CURRENT
|
± ACCURACY
|
RESOLUTION |
NOMINAL RANGE
|
| .4 to 20 ma |
0.1% of full scale |
0.004% |
4 to 20 ma |
| .0 to 20 ma |
0.1% of full scale |
0.004% |
0 to 20 ma |
| .0 to 10 ma |
0.2% of full scale |
0.008% |
0 to 10 ma |
A/D conversion rate is 10 per second
| .Notes: |
.*
.** |
Accuracy
includes linearization and cold junction tracking errors for a 50 ºF
to 104 ºF ambient temperature for thermocouple
inputs.
Resolutions shown are theoretical maximums, however, resolution is
programmable as is the position of the decimal point for engineering
ranges. A/D resolution is 1 part in 25,000 (approximately 15 Bit
plus sign) |
USER LINEARIZATION
A user defined linearization table is provided for
non-linear functions. In addition, the user can select a square root,
power 3/2 or power 5/2 function. All displays are in engineering units.
This feature is only available for voltage and current inputs.
FIELD TRANSMITTER SUPPLY
An internal 21 VDC supply to power two wire 4 to 20 ma
field transmitters is standard. A programmable excitation supply for
transducers is available as an option.

DM4000C - PULSE INPUT RATE or TOTAL
INDICATOR
The DM4000C
accepts all types of pulse inputs and provides a
choice of RATE or TOTAL displays. RATE is in engineering units and TOTAL
can have its own scaling. The TOTAL can be reset locally from the front or
remotely from an external contact and is stored during power down.
The instrument has two individual inputs channels 'a' and 'b'.
Either channel may be designed as the prime frequency input channel or
alternatively as the control channel. User selection of channels is
determined by the type of input.
Input signals accommodated by the channels are as follows:
| Input Type |
Channel |
| Volt free contact |
a, b |
| TTL Input |
b |
| 10 mv low level Input |
b |
| NAMUR compatible signals |
a |
| Open collector NPN |
b |
| Open collector PNP |
a |
Frequency Range
0.03 Hz to 50 Hz for potential free contacts
0.03 Hz to 20K Hz for all other input types
Debounce
A 4 ms Debounce is available to eliminate edge jitter for frequencies below 50
Hz.
Frequency Measurement
The incoming frequency is measured by a combination of period measurement and
pulse counting. A 100 ms window is used for all incoming frequencies above
10 Hz. This is called the capture window. For frequencies below 10
Hz the capture window becomes the actual incoming period. The following
table illustrates the point.
| .Frequency |
<0.03 |
0.03 to 10 |
10 to 20K |
20K to 25K |
| .Capture Window |
30 sec****** |
Period* & ****** |
100 mS |
| .Display***** |
Lo** |
Frequency Totalize*** |
Over**** |
| .Notes: |
.*
.**
.***
.****
.*****
.****** |
Period
is actual incoming period
Lo is engineering low range
Frequency and Total are scaled in engineering units
OVER is overrange
Display refresh rate is always 3.3 Hz
Capture window is halved when Debounce is selected (Below 50 Hz) |
Characterization
A 12 point user linearization table is provided as is selectable 'Cut lo'
feature which automatically sets the Rate to engineering low range for
frequencies that fall below this programmable value. Relay options may be
configured as alarms or pulse output if used in conjunction with total.
FIELD TRANSMITTER SUPPLY
An internal 8 VDC power supply to power field transmitters
is standard.

DM4000A - ANALOG INPUT FLOW COMPUTER
INDICATOR
The DM4000A
is a combination of the analog input
handling of the DM4000U with RATE and
TOTAL functions of the DM4000C
providing a special instrument designed for flow measurement applications.
The input can be either voltage or current and it is normally used in
conjunction with a differential pressure sensor and some type of restriction
e.g. orifice plate, flume, rectangular or 'V' weirs, to provide a digital
representation of flow.
DM4000A SPECIFICATIONS @ 68 °F
| Sensor |
± Accuracy |
Resolution |
Nominal Range |
| .Voltage |
| ± 10 Volts |
0.02% FS |
0.004% |
± 10 V |
| 1 to 5 Volts |
0.04% FS |
0.008% |
1V to +5 V |
| ± 1 Volt |
0.02% FS |
0.004% |
±1 V |
| ± 100 mv |
0.02% FS |
0.004% |
±0.1 V |
| .Current |
| 4 to 20 ma |
0.1% FS |
0.004% |
4 to 20 ma |
| 0 to 20 ma |
0.1% FS |
0.004% |
0 to 20 ma |
| 0 to 10 ma |
0.2% FS |
0.008% |
0 to 10 ma |
| .Characterization |
.Linear |
| .Square Root (Orifice
Plate) |
| .Power 3/2 (Rectangular
Weir/Flume) |
| .Power 5/2 (45 degree V
Weir) |
| .User: User defined 13
points |
| .Display |
.Rate: 5 digits |
| .Totalize: 6 digits + 6
overflow |
| .Special
Feature |
.Programmable 100 ms pulse
output |
| .(when option 01 or 02 are
fitted) |
The appropriate characterization can be selected from the front panel and the
display scaled in linear flow units. In addition, a 13 point user defined
characterization is available for the more unusual applications.
The display may be selected to show RATE or TOTAL; TOTAL having its own user
programmable scaling. When displaying flow RATE, totalizing is performed
in the background and pressing a front panel key provides a 'View' facility.
If TOTAL is selected as the main display, it is possible to 'View' the
instantaneous RATE.
Output options can be dedicated to either RATE or TOTAL and the TOTAL is
maintained during power down stored in EEPROM.
In addition, the relay output option can be configured as a pulse output
giving a contact closure for 100 ms every time there is a change in a particular
selectable digit on the TOTAL display, i.e. the contact will close for 100 ms
say every 100 gallons. This provides a low cost means of interfacing with
data logging systems or to drive additional secondary counters.
FIELD TRANSMITTER SUPPLY
An internal 21 VDC supply to power two wire 4 to 20 ma
field transmitters is standard. A programmable excitation supply for
transducers is available as an option.
DOWNLOADS
DM4000 Literature
ORDER CODE
DM4000(Type) / Option 1 / Option 2 / Comms
/ Supply
| .DM4000
Basic Model Number |
| .Type |
.U = Universal Input
.C = Pulse Input
.A =Flow Computer |
| .Options |
.01 = Single
programmable alarm relay 8 amps single pole.
.02 = Dual independently
programmable alarm relays 8 amps single pole, N/C (shared common).
.03 = 4 to 20 ma isolated
analog output or a voltage output by the addition of an external
resistor.
.04 = 2 to 20 VDC
programmable plus 24 VDC transducer excitation voltage. |
| .Communications |
.000 = No
Communications
.485 =RS485 comms - multi drop |
| .Supply |
.240 = 240 VAC 50/60
Hz
.120 = 120 VAC 50/60 Hz
...24 = 24 VAC 50/60 Hz |
ACCESSORIES
| ACC4000-01 |
Wall mounted enclosure to NEMA 4 |
| ACC4000-02 |
Adaptor for 1/4 to 1/8 DIN |
| ACC4000-03 |
Spare 3 way connector |
| ACC4000-04 |
Spare Handbook |
| ACC4000-05 |
Spare 5 way connector |
| ACC4000-06 |
Pack of 10 sealed gaskets |